Battery Monitoring System
Measurement Range | Battery Capacity : 5 ~ 6,000 Ah System Voltage : 0 ~ 576 VDC Load Current : ±3000 A Cell Voltage : 2, 4, 6, 8, or 12 VDC Internal Resistance : 0.010 ~ 99.999 mΩ Temperature : -20℃ ~ 90°C | |
---|---|---|
Accuracy / Resolution | System Voltage : ±0.5% / 0.1 V Load Current : ±1% / 0.1 A Cell Voltage : ±1% / 0.001 V Internal Resistance : ±2% / 0.001 mΩ Temperature : ±2% / 0.1 °C | |
I.R. (Internal Resistance) Measurement Speed | 3 seconds per cell | |
Data Acquisition | Measuring Interval : Adjustable from 10 min to 160 hours (voltage & I.R.) Data Transfer : TCP/IP, Modbus, DNP3 Internal Storage : No Internal Records | |
Software | Centroid Snet2 | |
Environment | Operating Temperature : 0 ~ 65 °C (32 ~ 150 °F) Relative Humidity : Under 80% | |
Power Requirements | Input Power : 48 VDC (36 ~ 72 V), 125 VDC (120 ~ 370 V), 100 ~ 240 VAC | |
Dimensions | Main Unit : 210 x 76 x 160 mm (8.27 x 3 x 6.3 in) Module : 114 x 70 x 39 mm (4.5 x 2.75 x 1.5 in) |